SiE-05C
Troubleshooting
Troubleshooting PLUS Series
317
3.21
Malfunction of Transmission Between Outdoor Units
Remote Controller
Display
UUU
U7777
Supposed Causes
Incorrect outdoor unit No. setting for constant speed type outdoor unit
Incorrect outdoor - outdoor unit transmission wiring connection (Q1Q2)
Incorrect function unit - outdoor unit external control adaptor transmission wiring connection
Incorrect C/H setting
Incorrect C/H unified address setting (function unit, outdoor unit external control adaptor)
Faulty function unit PC board
Faulty outdoor unit external control adaptor
Trobleshooting
Is the
constant speed
type outdoor unit outdoor
unit No. setting switch
(SS2) set correctly?
Is outdoor-outdoor
unit transmission wiring
normal?
C/H setting is set to "IND"
C/H is to be switched all
together.
C/H setting is set to
"MASTER"
C/H setting is set to
"SLAVE"
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
NO
Is indoor-outdoor unit
transmission wiring
normal?
Are the following items
normal?
Are the following items
normal?
Does the
malfunction occur again
when the C/H setting is
set to "IND"
YES
NO
Set the switch correctly and turn the
power back on.
Fix transmission wiring.
Fix indoor - outdoor unit
transmission wiring.
Function unit PC board replacement
Set C/H setting to "IND"
The same C/H unified address is
used for more than one outdoor unit
in outdoor - outdoor unit
transmission. Reset the address.
Fix faulty part.
Outdoor unit external control
adaptor replacement
Function unit PC board replacement
(VF155)
YES
YES
Outdoor unit external control adaptor
•
Is the adaptor receiving power?
•
Is the C/H unified address set correctly?
Outdoor unit (unified master unit)
•
Is the unit receiving power?
•
Is the C/H unified address set correctly?
SI-05C.BOOK Page 317 Monday, November 6, 2000 4:13 PM