Troubleshooting
SiE-05C
320
Troubleshooting PLUS Series
3.24
Malfunction of System, Refrigerant System Address Undefined
Remote Controller
Display
UUU
UHHH
H
Supposed Causes
Improper connection of transmission wiring between indoor unit and outdoor unit, or outdoor and
outdoor unit
Defect of indoor unit PC board
Defect of function unit PC board
Troubleshooting
Is
electricity
being introduce for
the first time after installation
or after an indoor or outdoor
unit PC board has
been replaced?
Is indoor-outdoor and
outdoor-outdoor unit
transmission wiring
normal?
After fixing incorrect wiring, push
and hold the RESET button on the
outdoor unit PC board for 5
seconds.
Does a malfunction occur?
Does a
"UH" malfunction occur
for all indoor units in
the system?
NO
NO
NO
NO
YES
NO
Does
a malfunction
occur even after 12
minutes elapses from the time
when electricity is introduced
to indoor and outdoor
units?
YES
YES
YES
YES
Normal
After fixing incorrect wiring, push
and hold the RESET button on
the outdoor unit PC board for 5
seconds.
∗
The unit will not run for up to
12 minutes.
Normal
Replace indoor unit PC board.
Replace function unit PC board.
(VF158)