SiE-05C
How to Use The Monitor Switch On The Inverter PC Board
Troubleshooting PLUS Series
323
5.2
Actuation of Fin Thermal
Remote Controller
Display
LLLL4444
Supposed Causes
Actuation of fin thermal (Actuates at min. 90˚C and resets at max. 80˚C)
Defect of inverter PC board
Defect of fin thermistor
Troubleshooting
YES
YES
Defect of power unit radiation
•
Intake port is clogged
•
Radiator fin is dirty
•
Outdoor temperature is high
Replace the thermistor.
Replace the inverter.
Characteristic
check of the radiator fin
thermistor (Refer to thermistor
characteristics
table.)
Temperature
of the radiator fin rises.
Actuates at min. 90˚C
Resets at max. 80˚C
Is reset possible?
Reset and operate.
NO
Abnormal
Normal
NO
(VF159)
SI-05C.BOOK Page 323 Monday, November 6, 2000 4:13 PM
Все каталоги и инструкции здесь:
http
:
//splitoff.ru/tehn-doc.html