How to Use The Monitor Switch On The Inverter PC Board
SiE-05C
324
Troubleshooting PLUS Series
5.3
Defect of Compressor Coil
Remote Controller
Display
LLLL5555
Supposed Causes
Defect of compressor coil (disconnected, defective insulation)
Compressor start-up malfunction (mechanical lock)
Defect of inverter unit
Troubleshooting
When you measure output voltage of an inverter, the reading is higher than the actual voltage.
YES
YES
Replace the compressor.
Replace the inverter unit.
Compressor inspection
Inspect according to the
diagnosis procedure for odd
noises, vibration and
operating status of the
compressor.
Disconnect the
the connection between
the compressor and
inverter.
The compressor's
coil is disconnected or the
insulation is defective.
Inverter
output voltage
check Inverter output
voltage is not balanced.
(Normal if within ±8 V [Y1, YAL])
(Note) Must be measured
when frequency is
stable.
After turning on again,
"L5" blinks again.
NO
NO
(VF160)
SI-05C.BOOK Page 324 Monday, November 6, 2000 4:13 PM