SiE-05C
Backup and Emergency Operation
Special Service Mode PLUS Series
333
Malfunctions for
which Backup
Operation can or
cannot Be
Executed
Malfunction
Malfunction Code
PC Board Type
EB9446~9A
EB9446~9B (Applies to items
manufactured from June on.)
Tripped Safety Device
E0
Cannot Operate
Can Operate
Faulty PC Board
E1
Cannot Operate
Cannot Operate
Tripped LPS
E4
Cannot Operate
Can Operate
Solenoid Valve Malfunction
E9
Cannot Operate
Can Operate
Discharge Pipe
Temperature Malfunction
F3
Cannot Operate
Can Operate
Faulty Control HPS
H3
Cannot Operate
Cannot Operate
Faulty Control LPS
H4
Cannot Operate
Cannot Operate
Air Thermistor Malfunction
H9
Can Operate
Can Operate
Discharge Pipe Thermistor
Malfunction
J3
Cannot Operate
Can Operate
Suction Pipe Thermistor
Malfunction
J5
Can Operate
Can Operate
Heat Exchange Thermistor
Malfunction
J6
Can Operate
Can Operate
Oil Temperature Thermistor
Malfunction
JH
Can Operate
Can Operate
Header Thermistor
Malfunction
J7
Can Operate
Can Operate
Reverse Phase / Negative
Phase
U1
Cannot Operate
Cannot Operate
Outdoor - L Transmission
Malfunction
U7
Cannot Operate
Cannot Operate