SiE-05C
Backup and Emergency Operation
Special Service Mode PLUS Series
335
Malfunctions for which emergency operation can or cannot be executed when an inverter type outdoor unit
malfunctions
2. When a constant speed type outdoor unit malfunctions
When a constant speed type outdoor unit malfunctions, you can continue to operate by setting to forced
backup operation in setting mode 2. With backup operation, you can continue to operate for up to 3 hours,
but there is no time restriction for this mode.
Malfunctions for which emergency operation can or cannot be executed when a constant speed type
outdoor unit malfunctions
Malfunction
Malfunction Code
Emergency Operation
Tripped Safety Device
E0
Can Operate
Faulty PC Board
E1
Cannot Operate
Tripped HPS
E3
Can Operate
Tripped LPS
E4
Can Operate
Solenoid Valve Malfunction
E9
Can Operate
Discharge Pipe Temperature Malfunction
F3
Can Operate
Air Thermistor Malfunction
H9
Can Operate
Discharge Pipe Thermistor Malfunction
J3
Can Operate
Suction Pipe Thermistor Malfunction
J5
Can Operate
Heat Exchange Thermistor Malfunction
J6
Can Operate
Oil Temperature Thermistor Malfunction
JH
Can Operate
Header Thermistor Malfunction
J7
Can Operate
High Pressure Sensor Malfunction
JA
Cannot Operate
Low Pressure Sensor Malfunction
JC
Cannot Operate
Faulty Inverter System
L0
Can Operate
Faulty Inverter Cooling
L4
Can Operate
Compressor Motor Ground Fault
L5
Can Operate
Compressor Overload, Disconnection
L8
Can Operate
Compressor Lock
L9
Can Operate
Inverter
Outdoor Unit PC Board Transmission Malfunction
LC
Can Operate
Power Supply Voltage Imbalance
P1
Can Operate
Power Unit Temperature Sensor Malfunction
P4
Can Operate
Reverse Phase / Negative Phase
U1
Cannot Operate
“Power Supply Voltage Malfunction, Instantaneous Failure”
U2
Can Operate
Indoor - Outdoor Unit Transmission Failure
U4
Cannot Operate
Outdoor
L Transmission Malfunction
U7
Cannot Operate
Malfunction
Malfunction Code
Emergency Operation
Tripped Safety Device
E0
Can Operate
Faulty PC Board
E1
Cannot Operate
Tripped LPS
E4
Can Operate
Solenoid Valve Malfunction
E9
Can Operate
Discharge Pipe Temperature Malfunction
F3
Can Operate
Faulty Control HPS
H3
Cannot Operate
Faulty Control LPS
H4
Cannot Operate
Air Thermistor Malfunction
H9
Can Operate
Discharge Pipe Thermistor Malfunction
J3
Can Operate
Suction Pipe Thermistor Malfunction
J5
Can Operate
Heat Exchange Thermistor Malfunction
J6
Can Operate
Oil Temperature Thermistor Malfunction
JH
Can Operate
Header Thermistor Malfunction
J7
Can Operate
Reverse Phase / Negative Phase
U1
Cannot Operate
Outdoor
L Transmission Malfunction
U7
Cannot Operate
SI-05C.BOOK Page 335 Monday, November 6, 2000 4:13 PM