Wiring Adaptor
SiE-05C
386
Appendix Inverter K Series / PLUS Series
Common Address
Setting (DS1 / DS2)
Decide the address for each control unit from 0~9 and set.
Note:
1. Setting is within 8 groups when using a cool/heat central remote controller. Set from No. 0~No. 7.
2. Be sure to make the address No. of the PC board adaptor described above match the address No. of
function unit or outdoor unit (BS unit if using cool/heat simultaneous selection type).
(For detailed settings, see the installation manual.)
Refer to the INSTALLATION INSTRUCTION.
Common Control
Input
Specifications
Input signal
Constant contact a
Input current is approx. 12 - 24 VDC, 10 mA per contact.
Use a micro-current contact for the relay contact.
(Max. 12 VDC, 1 mA)
Outside wiring specifications
Recommended electric wiring: Sheathed vinyl cord or cable 0.75~1.25 mm
²
(double core)
Wiring length: Max. 150 m
Run separate from power line in order to prevent malfunction.