Functions Inverter K Series
37
1.10
Control During Low Outdoor Air Temperature Cooling
When the outdoor air temperature is low in cooling operation, outdoor unit fans, electronic expansion valve
and compressors are controlled as follows in order to primarily maintain high pressure and to protect drop
in refrigerant circulation caused by drop in high pressure.
RSXY5K
RSXY8,10K
NOTE:
Step No. changes according to high pressure, low pressure and frequency.
(Step No. increases with reduction of high and low pressure.)
Low Outdoor Air Cooling IN Conditions (Steps 1-1, 2, 3)
Operating status
Electronic expansion valve
Fan
Frequency (Hz)
Normal operation
Fully open
H
Changes according to operating
status
Low outdoor temperature
cooling operation
Step 1
Fully open
L
76
Step 2
Fully open
OFF
48
Operating status
Electronic expansion valve
Fan
Frequency (Hz)
M1F M2F
8K
10K
Normal operation
Fully open
H
ON
Changes according to operating
status
Low outdoor temperature
cooling operation
Step 1-1
Fully open
L
ON
96
116
Step 1-2
Fully open
H
OFF
86
106
Step 1-3
Fully open
L
OFF
76
96
Step 2
Fully open
OFF OFF
60
76
Normal operation
Step 1-1
Step 1-2
«
carried out 30
continuous
seconds
«
carried out 30
continuous
seconds
¥
carried out 30
continuous
seconds
Step 1-3
¥
carried out 30
continuous
seconds
•
Cooling with compressor running
(doesn't include oil return)
&
•
High pressure < 10 kg/cm²
•
EV = 2000 pulses
(completely open)
or
•
High pressure > 14 kg/cm²
(1.372 MPa)
•
EV = 2000 pulses
(completely open)
or
•
High pressure < 14 kg/cm²
(1.372 MPa)
or
•
Low outdoor air cooling IN
conditions (Step 2)
Conditions satisfied
(VF006)
«
¥