Test Operation
SiE-05C
84
Test Operation Inverter K Series
NOTES:
1. Settings are made simultaneously for the entire group, however, if you select the mode No. inside
parentheses, you can also set by each individual unit. Setting changes however cannot be checked
except in the individual mode for those in parentheses.
2. The mode numbers inside parentheses cannot be used by wireless remote controllers, so they cannot
be set individually. Setting changes also cannot be checked.
3. Mode numbers 17 (27) and 19 (29) are HRV functions that can be set from a VRV system remote
controller.
4. The second code No. is factory set to “01.” The field set air flow direction position and thermostat
sensor in remote controller is however set to “02,” and ventilation fan speed is set to “05.”
5. Do not make settings other than those described above. Nothing is displayed for functions the indoor
unit is not equipped with.
6. “88” may be displayed to indicate the remote controller is resetting when returning to the normal mode.
1.12.3 Setting Contents and Code No.
For HRV settings, see the proper documents for HRV.
VRV
system
indoor
unit
settings
Mode
No.
Note 2
First
Code
No.
Setting Contents
Second Code No.(Note 3)
01
02
03
04
10(20)
0
Filter contamination heavy/
light (Setting for display time to
clean air filter)
(Sets display time to clean air
filter to half when there is
heavy filter contamination.)
Super
long life
filter
Light
Approx.
10,000
hrs.
Heavy
Approx.
5,000
hrs.
—
—
Long life
filter
Approx.
2,500
hrs.
Approx.
1,250
hrs.
Standard
filter
Approx.
200 hrs.
Approx.
100 hrs.
1
Long life filter type
(FXYC only, 01 indicates long life)
Long life filter
Super long life filter
—
Soot filter
2
Thermostat sensor in remote controller
Use
No use
—
3
Display time to clean air filter calculation
(Set when filter sign is not to be displayed.)
Display
No display
—
12(22)
0
Optional accessories output selection (field
selection of output for adaptor for wiring)
Indoor unit turned
ON by thermostat
Operation output
Malfunction output
1
ON/OFF input from outside (Set when ON/
OFF is to be controlled from outside.)
Forced OFF
ON/OFF control
External protection
device
—
2
Thermostat differential changeover
(Set when remote sensor is to be used.)
FXYC, FXYE, FXYF, FXYK, FXYH only
1˚C
0.5˚C
—
—
3
OFF by thermostat fan speed
LL
Set fan speed
—
—
4
Automatic mode differential (automatic
temperature differential setting for VRV
system heat recovery series cool/heat)
01:0
02:1
03:2
4:03
05:4
6:05
7:06
08:7
5
Power failure automatic reset
Not equipped
Equipped
—
—
13(23)
0
High air outlet velocity
(Set when installed in place with ceiling
higher than 2.7 m.) FXYF only
N
H
—
—
1
Selection of air flow direction
(Set when a blocking pad kit has been
installed.) FXYF only
F (4 directions)
T (3 directions)
W (2 directions)
—
2
Horizontal air discharge
Equipped
Not equipped
—
3
Air flow direction adjustment (Set at
installation of decoration panel.) FXYK only
Equipped
Not equipped
—
4
Field set air flow position setting
Draft prevention
Standard
Ceiling Soiling
prevention
—
5
Field set fan speed selection
(fan speed control by air discharge outlet
for phase control)
Standard
Optional
accessory 1
Optional accessory
2
—
15(25)
1
Thermostat OFF excess humidity
Not equipped
Equipped
—
—
3
Drain pump humidifier interlock selection
Not equipped
Equipped
—
—
4
Sets whether filter sign is to be output by
time or by input.
Time addition
Input
—
—
5
Field set selection for individual ventilation
setting by remote controller
Not equipped
Equipped
—
—
6
Field set selection for individual ventilation
setting by remote controller
Not equipped
Equipped
—
—