SiE-05C
Test Operation
Test Operation Inverter K Series
85
1.13
Centralized Control Group No. Setting
If carrying out centralized control by central remote controller or unified ON/OFF controller, group No.
must be set for each group individually by remote controller.
Group No. setting by remote controller for centralized control
1. When in the normal mode, push the
button for 4 seconds or more, and operation then enters
the “field setting mode.”
2. Set mode No. “00” with the
button.
∗
3. Push the
button to inspect the group No. display.
4. Set the group No. for each group with the
button (The group No. increases in the manner of 1-00,
1-01, ...,1-15, 2-00,...4-15. However, the unified ON/OFF controller displays only the group No. within
the range selected by the switch for setting each address.)
5. Push the timer
button to define the selected group No.
6. Push the
button to return to the normal mode.
Even if not using a remote controller, connect the remote controller when setting the group No., set the
group No. for centralized control, and disconnect after making the setting.
Set the group No. after turning on the power supply for the central remote controller, unified ON/OFF
controller, and indoor unit.
SI-05C.BOOK Page 85 Monday, November 6, 2000 4:13 PM