SiE33-102
Appendix
General Information
111
During operation
System name
Inspection item
Inspection method
Standard (guideline)
Decision
Measurement values
Main power supply voltage
Operation circuit voltage
Fan rotation direction
Fan noise/vibration
Fan operation current
Suction air temperature
Discharge air temperature
Compressor discharge pressure
Compressor suction pressure
Compressor operating current
Compressor operating frequency
Suction pipe temperature
Discharge pipe temperature
Crank case heater
Fan rotation direction
Fan noise/vibration
Fan operating current
Suction air temperature
Discharge air temperature
Tester
Tester
Visual inspection
Listening
Clamp meter
Thermometer
Thermometer
Pressure gauge
Pressure gauge
Clamp meter
Clamp meter
Thermometer
Thermometer
Touch
Visual inspection
Listening
Clamp meter
Thermometer
Thermometer
Rated voltage
±
10%
Rated voltage
±
10%
Forward rotation
No noise or vibration
Temperature differential
9~11˚C when cooling, 2~3.5˚C when heating
Phase differential within 1A
3~15˚C
85~105˚C
Warm
Forward rotation
No noise or vibration
Temperature differential
9~11˚C when cooling, 2~3.5˚C when heating
V
G NG
M1(11)F, M2(12)F, M21F, M22F
A A A A
˚C
˚C
INV Mpa
STD1 Mpa
STD2 Mpa
Mpa
INV A
STD1 R( )A, S( )A, T( )A
STD2 R( )A, S( )A, T( )A
INV Hz
INV G·NG
STD1 G·NG
STD2 G·NG
G NG
A
˚C
˚C
Main unit
Sub unit
(V1093)
INV ˚C
STD2 ˚C
INV ˚C
STD2 ˚C
STD1 ˚C
STD1 ˚C
R-S V S-T V R-T V
Si33-102.book Page 111 Tuesday, June 26, 2001 3:18 PM
Все каталоги и инструкции здесь:
http
:
//splitoff.ru/tehn-doc.html