Unpacking and Placing the Unit
SiE33-102
140
Installation Manual
5. Unpacking and Placing the Unit
5.1
Unpacking and Placing the Unit
1. Remove the wooden crate from the unit.
2. Remove the four screws fixing the unit to the pallet.
3. The unit must be installed on a solid longitudinal foundation (steelbeam frame or concrete) as indicated
in below figure.
Note:
Maximum height of the foundation is 150mm.
4. Lift the unit from the pallet and place it on its installation position.
5. Fasten the unit in place using four anchor bolts M12.
6. Remove the upper and lower service plate.
7. When closing the service panels take care that the tightening torque does not exceed 4.1 Nm.
8. Remove the yellow shipping stays from the compressor support as shown in the figure (2 stays per
single compressor). Tighten the installation bolts firmly again afterwards.
Caution
1. Prepare a water drainage channel around the foundation to drain waste water from around the unit.
2. If the unit is to be installed on a roof, check the strength of the roof and its drainage facilities first.
3. If the unit is to be installed on a frame, install the waterproofing board within a distance of 150mm under
the unit in order to prevent infiltration of water coming from under the unit.
Refer “Installation of Outdoor Unit” page 55 for more foundation detail.
1280
1000
1280
1000
80
80
688
726
750
2568
2290
1280
1000
80
688
726
760
80
(V1888)
Fundamental bolt position (
φ
15 holes ... 8 places)
Fundamental bolt position (
φ
15 holes ... 8 places)
Do not use stands to
support the corners.
Wrong
Wrong
(V1838)
(V0898)