Field Wiring
SiE33-102
162
Installation Manual
7.6.9
Picking Power Line and Transmission Line
Be sure to let the power line and the transmission line pass through a conduit hole.
Pick the power line from the upper hole on the left side plate, from the front position of the main unit
(through the conduit hole of the wiring mounting plate - optional parts) or from a knock out hole to be
made in the unit’s bottom plate.
If you pick the power line from the front position of the unit, proceed as follows and refer to figure:
Pick the transmission line from the middle positioned conduit hole on the left side plate, or from the front
position of the main unit (after binding it to the piping with finishing tape as in below figure).
Caution
Be sure to keep the power line and transmission line apart from each other.
Be careful about polarity of the transmission line.
Make sure that the transmission line is clamped as shown in the figure in chapter “Field line connection”.
Check that wiring lines do not make contact with refrigerant piping.
Firmly close the lid and arrange the electrical wires so as to prevent the lid or other parts from coming
loose.
Remove the lower frontplate (1), punch a hole in the knock hole and cut the
hole (2) all the way to the slit.
Attach the 3 sealing pads (optional parts) (3) on the wiring mounting plate
(optional parts) (4) corresponding to the overlapped area of the front plate.
Install the wiring mounting plate to the front side of the side plate with the 2
delivered screws.
RSXY16,18,20
Insulation material
Gas line
Cable(High voltage)
Insulation material
Liquid line
Cable (Low voltage)
Branch wiring
between outdoor
units (low voltage)
Branch wiring
between outdoor
units (high voltage)
Branch wiring
between indoor
and outdoor units.
Separate
Power
cord
Cut out
the diagonal
line area
Through -slot
cover
RXE8,10
(Sub unit)
RXY8,10
(Main unit)
Separate
(V1865)
RSXY24,26,28,30
Insulation material
Gas line
Cable(High voltage)
Insulation material
Liquid line
Cable(Low voltage)
Branch wiring
between outdoor
units (low voltage)
Branch wiring
between outdoor
units (high voltage)
Branch
wiring
between
indoor
and
outdoor
units.
Separate
Power
cord
Cut out
the diagonal
line area
Through -slot
cover
RXE8,10
(Sub unit)
RXY16,20
(Main unit)
Separate
(V1866)
1
2
3
4
(V1867)
Liquid side pipe
Gas side pipe
Pipe heat insulation
Finishing tape
Pipe heat
insulation
Transmission line
(V1868)
Si33-102.book Page 162 Tuesday, June 26, 2001 3:18 PM