Installation
SiE33-102
24
General Information
Not
recommendable
but in case of
emergency
You must use a torque wrench but if you are obliged to install the unit without a torque wrench, you may
follow the installation method mentioned below.
After the work is finished, make sure to check that is no gas leak.
When you keep on tightening the flare nut with a spanner, there is a point where the tightening torque
suddenly increases. From that position, further tighten the flare nut the angle shown below:
Pipe size
Further tightening angle
Recommended arm length of tool
6.4 (1/4”)
60 to 90 degrees
Approx. 150mm
9.5 (3/8”)
60 to 90 degrees
Approx. 200mm
12.7 (1/2”)
30 to 60 degrees
Approx. 250mm
15.9 (5/8”)
30 to 60 degrees
Approx. 300mm
19.1 (3/4”)
20 to 35 degrees
Approx. 450mm