SiE33-102
Installation
General Information
35
Drain Trap
Fit any indoor unit whose drain pipe connection is subjected to negative pressure, with a drain trap.
(FXYM40~125 only)
a) Rig the drain trap as shown in the drawing bellow.
b) Provide one trap per unit. A single trap for converging units will prove ineffective.
c) Rig the trap to allow for future cleaning.
Grouped Drain
Piping
1. It is standard work practice to make connections to the main pipe from above. The pipe down from the
combination should be as large as possible.
2. The pipework should be kept as short as possible and the number of indoor units per group kept to a
minimum.