SiE33-102
Installation
General Information
51
FXYM-KF-Outdoor Air Processing Unit
1. Install the drain pipes.
Keep piping as short as possible and slope it downwards so that air may not remaine trapped inside the
pipe.
The diameter of the piping is the same as that of the connecting pipe (PS1B), and should be kept equal
to or greater than that of the connecting pipe.
Insulate the drain hose inside the building.
There is negative pressure inside the unit relative to atmospheric pressure when the unit is
running, so be sure to provide drain frap on the drain outlet. (See the figure)
In order to prevent foreign matter from building up inside the piping, you should avoid curves
as much as possible, and arrange so the trap can be cleaned.
Example drain trap installation
If directly connected to the unit:
Note:
Be sure to insulate both sides of the drain trap connections.
Install the drain trap so that the gap for cleaning is straight below. (±20˚ or less)
If installing central drain piping, install according to the following figure.
2. After piping work is finished, check drainage flows smoothly.
3.2.10 Electrical Work
Control Wiring
1. Compatible types of wire
Wiring Specifications
Notes:
1. Sheathed wire may be used for transmission winings, but they do not comply with EMI (Electromagnetic
lnterference) (EN55014). When using sheathed wire. EMI must conform to Japanese standards
stipulated in the Electric Appliance Regulatory Act. (If using a sheathed wire, the grounding shown in
the figure on the left is unnecessary.)
2. For FXYA indoor unit, use sheathed wire.
2. Problems arising from the use of unsuitable cable
a) When cable less than 0.75 mm
²
is used
Where the control wiring is particularly long the transmission signals may, for example, become
unstable and the terminal relay cease to function. (Reduced voltage) The control system may become
unduly subject to noise interference.
Insulation
(attached)
Mark for aligning insulation and fitting
Insulation for drain trap fitting
(attached)
Blind cap
(To keep line clean)
Drain trap
(attached)
Insulation (attached)
3PA60998-14P-6
100mm
or more
3PA60998-14P-7
Wiring Type
Shield Wire (2 wire) (See NOTE 1, 2)
Size
0.75~1.25 mm
²
Si33-102.book Page 51 Tuesday, June 26, 2001 3:18 PM