Installation
SiE33-102
56
General Information
Caution in installation
1. Execute the installation work by checking the foundation strength and levelness to avoid any
occurrence of vibration and noise.
Fix the unit tightly with foundation bolts. (Prepare 4 sets of M12 foundation bolts with proper nuts and
washers.)
The proper length of the foundation bolts form the surface of the base is 20mm.
The foundation must support the unit in the range above the shaped portion in the figure 1.
2. Remove the fitting (yellow color) for loading as shown in the figure 2.
Tighten the installation bolt of compressor firmly again.
2 fittings are attached to the front side of a single compressor.
Caution
Install the unit securely in case of earthquake an typhoon, cyclone, hurricane or other strong wind. The unit
may topple or cause another accident if improperly set up.
Unpacking and
Placing the Unit
1. Remove the wooden crafte from the unit.
2. Remove the four screws fixing the unit to the pallet.
3. The unit must be installed on a solid longitudinal foundation (steelbeam frame or concrete) as indicated
in figure 1.
Bad Example
Note:
Maximum height of the foundation is 150mm.
1280
1000
1280
1000
80
80
688
726
750
2568
2290
1280
1000
80
688
726
760
80
(V1888)
Fundamental bolt position (
φ
15 holes ... 8 places)
Fundamental bolt position (
φ
15 holes ... 8 places)
Do not use stands to
support the corners.
Wrong
Wrong
(V1838)
Si33-102.book Page 56 Tuesday, June 26, 2001 3:18 PM
Все каталоги и инструкции здесь:
http
:
//splitoff.ru/tehn-doc.html