SiE33-102
Product Outline
General Information
5
1.3
Model Configuration and Combination
Number of units and capacity of connectable indoor units
Y1 : 3 phase, 380~415V, 50Hz
YAL : 3 phase, 380V, 60Hz
(E) : Salt damage resistant specifications
Connectable indoor unit
VE : 1 phase, 220~240V/220V, 50/60Hz
V1 : 1 phase, 220~240V, 50Hz
VAL : 1 phase, 220V, 60Hz
Indoor unit capacity
Use the above tables to determine the capacities of indoor units to be connected. Make sure the total
capacity of indoor units connected to each outdoor unit is within the specified value (kW).
The total capacity of connected indoor units must be within a range of 50 to 130% of the rated capacity
of the outdoor unit.
In some models, it is not possible to connect the maximum number of connectable indoor units. Select
models so the total capacity of connected indoor units conforms to the specification.
Standard
series
Equivalent output
16HP
18HP
20HP
24HP
R-22 VRV PLUS series system model
RSXY16KAY1(E)/
YAL(E)
RSXY18KAY1(E)/
YAL(E)
RSXY20KAY1(E)/
YAL(E)
RSXY24KAY1(E)/
YAL(E)
Outdoor unit combination
Main unit
RXY8KAY1(E)/
YAL(E)
RXY10KAY1(E)/
YAL(E)
RXY10KAY1(E)/
YAL(E)
RXY16KAY1(E)/
YAL(E)
Sub unit
RXE8KAY1(E)/
YAL(E)
RXE8KAY1(E)/
YAL(E)
RXE10KAY1(E)/
YAL(E)
RXE8KAY1(E)/
YAL(E)
Total number of connectable indoor units
Up to 20 units
Up to 32 units
Total capacity of connectable indoor units
200~520
225~585
250~650
300~780
Standard
series
Equivalent output
26HP
28HP
30HP
R-22 VRV PLUS series system model
RSXY26KAY1(E)/
YAL(E)
RSXY28KAY1(E)/
YAL(E)
RSXY30KAY1(E)/
YAL(E)
Outdoor unit combination
Main unit
RXY16KAY1(E)/YAL(E)
RXY20KAY1(E)/YAL(E)
RXY20KAY1(E)/YAL(E)
Sub unit
RXE10KAY1(E)/YAL(E)
RXE8KAY1(E)/YAL(E)
RXE10KAY1(E)/YAL(E)
Total number of connectable indoor units
Up to 32 units
Total capacity of connectable indoor units
325~845
350~910
375~975
Indoor unit
Model name
Ceiling
mounted
cassette unit
2-way blow
FXYC20KVE·25KVE·32KVE·40KVE·50KVE·63KVE·80KVE·125KVE
4-way blow
FXYF25KBVE·32KBVE·40KBVE·50KBVE·63KBVE·80KBVE·100KBVE·125KBVE
Corner type
FXYK25KV1/VAL·32KV1/VAL·40KV1/VAL·63KV1/VAL
Ceiling mounted low silhoutte duct
unit
FXYD20KAVE·25KAVE·32KAVE·40KAVE·50KAVE·63KAVE
Concealed ceiling unit
FXYS20KV1/VAL·25KV1/VAL·32KV1/VAL·40KV1/VAL·50KV1/VAL·63KV1/VAL·80KV1/VAL·100KV1/
VAL·125KV1/VAL
Concealed ceiling unit
FXYB20KV1·25KV1·32KV1·40KV1·50KV1·63KV1·80KV1·100KV1·125KV1·
Concealed ceiling unit (large)
FXYM40KVE·50KVE·63KVE·80KVE·100KVE·125KVE·200KJVE·250KJVE
Ceiling suspended unit
FXYH32KVE·63KVE·100KVE
Wall mounted unit
FXYA25KVE·32KVE·40KVE·50KVE·63KVE
Floor standing unit
FXYL20KJVE·25KJVE·32KJVE·40KJVE·50KJVE·63KJVE
Concealed floor standing unit
FXYLM20KJVE·25KJVE·32KJVE·40KJVE·50KJVE·63KJVE
New refrigerant model code
20 type
25 type
32 type
40 type
50 type
63 type
80 type 100 type 125 type 200 type 250 type
Selecting model capacity
2.2kW
2.8kW
3.5kW
4.5kW
5.6kW
7.0kW
9.0kW
11.2kW
14.0kW
22.4kW
28.0kW
Equivalent output
0.8HP
1HP
1.25HP
1.6HP
2.0HP
2.5HP
3.2HP
4HP
5HP
8HP
10HP
Part1.fm Page 5 Wednesday, July 4, 2001 11:53 AM