Field Settings for Indoor Unit
SiME332106E
94
Part 5 Field Settings and Test Operation
When the unit is equipped with an infrared presence/floor sensor:
: Factory setting
Refer to
Compensating the temperature around people
Note that the control is automatically switched to the one performed only by the suction air
thermistor for indoor unit when the Second code No. is
01
during the group control.
To use the remote controller thermistor control during group control, select the Second code No.
02
in First code No.
6
.
Mode No.
First Code No.
Second Code No.
Contents
10 (20)
6
01
Remote controller thermistor control is not
permitted during group control
02
Remote controller thermistor control is
permitted during group control
20
22
24
26
28
30
32
34
36
21
19
17
23
25
27
29
31
33
35
37
14
16
18
20
22
24
26
28
30
32
14
16
18
20
22
24
26
28
30
32
34
In cooling
In heating
Suction air temperature (°C)
Suction air temperature (°C)
Suction air
thermistor
Suction air
thermistor
Suction air
thermistor
Suction air
thermistor
Suction air
thermistor
Suction air
thermistor
Suction air
thermistor
Suction air
thermistor
Remote controller
thermistor
Remote controller
thermistor
Remote controller
thermistor
Remote controller
thermistor
Set temper
ature (°C)
Set temper
ature (°C)
Mode No.
Second Code No.
10 (20)
2
01
02
02
02
#
02
03
11 (21)
8
01
01
02
03
#
04
01
The thermistor to be used
Remote controller thermistor
—
—
—
—
Suction air thermistor
—
Infrared floor sensor
—
—
—
First Code No.
The infrared floor
sensor is not used
Priority given to
the suction air
temperature (
)
Only the remote
controller thermistor
is used
Priority given to the
floor temperature (
)
Only the suction air
thermistor is used
Standard setting
(Factory setting)