Field Settings for Indoor Unit
SiME332106E
96
Part 5 Field Settings and Test Operation
1.4.6 Dry Operation Time during VRTsmart Control
If you switch the operation mode to "Dry" while VRTsmart is enabled, the mode will
automatically switch to "Cooling" after a certain period of time is elapsed.
If you want to increase the duration of dry operation, change the Second code No. as
indicated in the following table.
Note 1) Increasing duration of dry operation degrades the energy efficiency
: Factory setting
Note 2) When group control is enabled, all indoor units in the same group have a same set value for
duration of dry operation.
1.4.7 Low Airflow Setting when Thermostat OFF during VRTsmart Control
This setting changes the airflow volume to LL in coordination with the VRTsmart control when
cooling thermostat OFF is set. Also, the airflow direction is changed to horizontal.
When disabled:
12 (22)-6 (the airflow volume setting when cooling thermostat OFF is enabled)
13 (23)-7 (the swing setting when cooling thermostat OFF is enabled) is as set
When enabled: LL when Te ≥ 7°C
: Factory setting
1.4.8 Indoor Fan Settings during Cooling/Heating Thermostat OFF
: Factory setting
1.4.9 Setting of Airflow Rate when Heating
The fan revolution is changed to maintain the sufficient distance for warm air to reach during the
heating operation. The setting should be changed depending on the installation condition of the
unit.
: Factory setting
Note that this setting is effective only during the heating operation.
Mode
No.
First
Code No.
Second
Code No.
Contents
10 (20)
10
01
30 minutes
02
60 minutes
03
90 minutes
04
Continuous (not returning to cooling)
Mode
No.
First Code
No.
Second
Code No.
Contents
10 (20)
11
01
Disabled
02
Enabled
Mode
No.
First Code No. Second Code
No.
Contents
11 (21)
2
01
Normal
02
Fan OFF
Mode
No.
First Code
No.
Second Code
No.
Contents
11 (21)
3
01
Standard
02
Slightly increased
03
Increased