SiME332106E
Field Settings for Indoor Unit
Part 5 Field Settings and Test Operation
99
1.4.15 External ON/OFF Input
This input is used for "ON/OFF operation" and "Protection device input" from the outside. The
input is performed from the T1-T2 terminal of the operation terminal block in the electrical
component box.
: Factory setting
1.4.16 Thermostat Differential Changeover
Set when remote sensor is to be used.
Differential value during thermostat ON/OFF control can be changed.
: Factory setting
1.4.17 Airflow Setting when Heating Thermostat is OFF
This setting is used to set airflow when heating thermostat is OFF.
When thermostat OFF airflow volume up mode is used, careful consideration is required
before deciding installation location.
: Factory setting
1.4.18 Automatic Mode Differential
This setting makes it possible to change differential values for mode selection while in automatic
operation mode.
: Factory setting
The automatic operation mode setting is made by the use of the "Operation Mode Selector"
button.
Mode
No.
First
Code No.
Second
Code No.
Contents
12 (22)
1
01
ON: Forced OFF (prohibition of using the remote controller)
OFF: Permission of using the remote controller
02
OFF
ON: Operation
ON
OFF: Stop
03
ON: Operation
OFF: The system stops, then the applicable unit indicates
A0
. The
other indoor units indicate
U9.
F2 T1 T2
Forced OFF
Input A
Mode
No.
First Code
No.
Second
Code No.
Contents
12 (22)
2
01
1ºC
02
0.5ºC
Mode
No.
First Code
No.
Second
Code No.
Contents
12 (22)
3
01
LL tap
02
Set fan speed
Mode No.
First Code
No.
Second Code No.
01
02
03
04
05
06
07
08
12 (22)
4
0°C
1°C
2°C
3°C
4°C
5°C
6°C
7°C