Field Settings for Indoor Unit
SiME332106E
102
Part 5 Field Settings and Test Operation
Note(s)
1.4.24 Swing Pattern Settings
Set the flap operation in swing mode.
With the factory swing, flaps facing each other are synchronized to operate, and flaps placed
side by side are set to swing in an opposite direction to agitate airflow to reduce temperature
irregularity.
Conventional swing operation (all direction synchronized swing) can be set onsite.
: Factory setting
1.4.25 Airflow Direction Adjustment Range
Make the following airflow direction setting according to the respective purpose.
1. Some indoor unit models are not equipped with draft prevention (upward) function.
2. When the model FXFSQ-AR is attached with a closing member kit, set the Second Code No.
to
02
or
03
.
1.4.26 Setting of Static Pressure Selection
FXDQ-PD, FXDQ-ND
: Factory setting
Mode
No.
First
Code No.
Second
Code No.
Contents
13 (23)
2
01
All direction synchronized swing
02
—
03
Facing swing
FXFSQ-AR, FXAQ-AR
: Factory setting
Mode
No.
First
Code No.
Second
Code No.
Contents
13 (23)
4
01
Draft prevention (Upward)
02
Standard
03
Ceiling soiling prevention (Downward)
Model
No.
First Code
No.
Second
Code No.
Contents
13 (23)
5
01
Standard (10 Pa)
02
High static pressure (30 Pa)