Field Settings for Outdoor Unit
SiME332106E
110
Part 5 Field Settings and Test Operation
(1) Microcomputer normal monitor
This monitor blinks while in normal control, and turns ON or OFF when an error occurs.
(2) 7 segment display
Used to check the transmission.
Used to display the transmission state between indoor and outdoor units.
Used to display the contents of error.
Used to display the contents of field setting.
(3) BS button
Used to change mode.
(4) DIP switch
Used to make field settings.
The figure below shows the required position of the DIP switches on spare PCB. Change DIP
switches at time of power disconnected.
RXYMQ4-6AYFK
(3) BS button (BS1~BS3)
(2) Segment display (SEG1~SEG3)
(4)
DIP switch
(DS1-1~4)
(DS2-1~4)
(1)
Microcomputer
normal monitor
(HAP)
Connection terminal
for transmission use
ON
OFF
1
2
3
4
DS1
Initial position of DIP switches (
)
1
2
3
4
DS2
Application model The setting method (
represents the position of switches)
RXYMQ4AVMK
Set DS1-2, DS1-4, DS2-1, and DS2-3 to ON.
RXYMQ4AYFK
RXYMQ5AYFK
RXYMQ6AYFK
Set DS1-2, DS1-4, DS2-1, DS2-2, and DS2-3 to
ON
ON
OFF
1 2 3 4
1 2 3 4
DS2
DS1
ON
OFF
1 2 3 4
1 2 3 4
DS1
DS2