SiME332106E
Field Settings for Outdoor Unit
Part 5 Field Settings and Test Operation
119
2.6.2 Overview of Setting Mode (Mode 2)
This overview shows the available settings by using the press buttons on the outdoor unit PCB.
No.
Item
Contents
Description
Display
Description
Display
SEG
1
SEG
2
SEG
3
SEG
1
SEG
2
SEG
3
2
Low noise/
demand address
Used to make address setting for low
noise/demand address.
2.
0
2
Address:
0
~
31
3
0
1
5
Indoor fan
forced H
Used to force the fan of indoor unit to H
tap.
2.
0
5
Normal operation
Indoor fan H
0
1
6
Forced
thermostat ON
Used to force all indoor units to operate
forced thermostat ON.
2.
0
6
Normal operation
Forced thermostat ON
0
1
8
Te setting
Used to make setting of targeted
evaporating temperature for cooling
operation.
2.
0
8
Standard: 6°C
High sensible: 7°C
High sensible: 8°C
High sensible: 9°C
High sensible: 10°C
High sensible: 11°C
2
3
4
5
6
7
9
Tc setting
Used to make setting of targeted
condensing temperature for heating
operation.
2.
0
9
Low sensible: 41°C
Standard: 43°C
High sensible: 46°C
1
3
6
10
Defrost selection
setting
Used to adjust the defrost start
temperature of outdoor coil, to initiate
defrosting earlier/later.
2.
1
0
Defrost IN –2°
Normal
Defrost IN +2°
0
1
2
11
Eco setting is available from an external input.
When this configuration is set, it is not possible to turn the
Eco refrigerant control ON/OFF using the remote
controller. Also, depending on the settings, low noise
operation or demand operation may not be performed
using the external control adaptor.
2.
1
1
Unavailable
Low noise level input
Demand input
0
1
2
12
External low
noise/demand
setting
Used to receive external low noise or
demand signal.
2.
1
2
Input LNO/DE
OFF
ON
0
1
13
AIRNET
address
Used to set address of AIRNET
2.
1
3
Address:
0
~
63
6
0
3
18
High EST mode
for outdoor fan
High external static pressure mode
setting
2.
1
8
ON (Auto adjust and
re-judge)
OFF (Auto adjust without
re-judge)
Forced level 0
Forced level 1
Forced level 2
0
1
2
3
4
21
Refrigerant
recovery/
vacuuming
Used to set the system to refrigerant
recovery mode (without compressor
run).
2.
2
1
Refrigerant recovery
OFF
ON
0
1
22
Automatic
night-time low
noise operation
Automatic night-time low noise
operation. Time for the operation is
subject to the start and end time
settings.
2.
2
2
OFF
Level 1
Level 2
Level 3
0
1
2
3
23
Used to set Eco mode invalid.
When this configuration is set, it is not possible to turn the
Eco mode ON/OFF using the external control adaptor.
2.
2
3
Valid
Invalid for cooling
Invalid for heating
Invalid
0
1
2
3