SiME332106E
Field Settings for Outdoor Unit
Part 5 Field Settings and Test Operation
121
Setting does not return to factory setting when exit mode 2. To cancel the function, change
setting manually to factory setting.
Once function is activated
t01
appears. To stop current function, press once BS3 “Return”
button.
For detailed description about each setting, refer to
Details of Setting Mode (Mode 2)
on page
122.
Indication
bold
means factory setting.
No.
Item
Contents
Description
Display
Description
Display
SEG
1
SEG
2
SEG
3
SEG
1
SEG
2
SEG
3
76
VRTsmart
control
Te upper limit
Used to change upper limit of target
evaporation temperature in VRTsmart
control.
2.
7
6
Low 1
Low 2
Low 3
Low 4
Low 5
Low 6
Standard
High
0
1
2
3
4
5
6
7
77
VRTsmart
control
Tc lower limit
Used to change lower limit of target
condensation temperature in VRTsmart
control.
2.
7
7
Low
Standard
High 1
High 2
High 3
High 4
High 5
High 6
0
1
2
3
4
5
6
7
78
VRT control
Te upper limit
Used to change upper limit of target
evaporation temperature in VRT
control.
2.
7
8
Standard
High
4
6
79
VRT control
Tc lower limit
Used to change lower limit of target
condensation temperature in VRT
control.
2.
7
9
Standard
Low
2
3
81
Cooling comfort setting
2.
8
1
ECO
Mild
Quick
Powerful
0
1
2
3
82
Heating comfort setting
2.
8
2
ECO
Mild
Quick
Powerful
0
1
2
3
83 Master remote control setting when mix combination
2.
8
3
VRV
indoor
RA indoor
—
—
0
1
84
Initial indoor EV
opening
Initial indoor electronic expansion valve
opening at heating thermostat ON
2.
8
4
400 pulse
500 pulse
600 pulse
300 pulse
0
1
2
3
90
Indoor unit
without power
Possible for operate system when
some indoor units are temporary
without power supply.
2.
9
0
Disabled
Enabled
0
1
95
Eco level setting for VRTsmart
2.
9
5
Standard
Middle
High
0
1
2
96
Eco level setting for Eco mode by main PCB
2.
9
6
OFF
Low
Standard
0
1
2