Field Settings for Outdoor Unit
SiME332106E
134
Part 5 Field Settings and Test Operation
Image of operation in the case of A
Image of operation in the case of B
Image of operation in the case of A and B
Power consumption
Rated
80%
40%
Forced thermostat OFF
(Fan operation)
60%
70%
Demand level 1
instructing
Power consumption set by
"Demand 1 level setting".
Demand level 2
instructing
Demand level 3
instructing
The power
consumption
during the
demand level 1
instructing can be
set with the
"Demand 1 level
setting".
("70% of rated
power
consumption" has
been set at
factory.)
The power consumption set with "Demand 1 level setting".
When the
"Normal demand
setting" is set to
ON ("OFF" has
been set at
factory.), the
power
consumption can
be set with the
"Demand 1 level
setting". ("70% of
rated power
consumption" has
been set at
factory.)
Power consumption
Rated
80%
70%
60%
The power consumption set with
"Demand 1 level setting".
#
Demand level
2 instructing
#
Demand level
3 instructing
The power
consumption can
be set with the
"Demand 1 level
setting". ("70% of
rated power
consumption" has
been set at
factory.)
#
During constant demand
operation, when the
external demand
instruction is received, the
instruction with higher
demand level has the
precedence.
Power consumption
Rated
Forced thermostat OFF
(Fan operation)
40%
60%
70%
80%