SiME332106E
Troubleshooting by Error Code
Part 6 Service Diagnosis
161
5.4 Indoor Unit PCB Abnormality
Applicable
Models
All indoor unit models
Error Code
A1
Method of Error
Detection
Data from EEPROM is checked.
Error Decision
Conditions
Data cannot be correctly received from the EEPROM
EEPROM: Type of nonvolatile memory. Maintains memory contents even when the power
supply is turned OFF.
Supposed
Causes
Defective indoor unit control PCB
External factor (Noise etc.)
Troubleshooting
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Turn the power supply OFF,
then the power ON again.
Does the
system return to
normal?
The indoor unit control
PCB (A1P) is normal.
External factor other than
error (for example, noise
etc.).
Replace the indoor unit
control PCB (A1P).
NO