SiME332106E
Troubleshooting by Error Code
Part 6 Service Diagnosis
185
5.17 Combination Abnormality (between Indoor Unit PCB and
Fan PCB)
Applicable
Models
FXMQ-PB
Error Code
C6
Method of Error
Detection
Transmission conditions with the fan PCB (A2P) are checked using the indoor unit PCB (A1P).
Error Decision
Conditions
Fan PCB (A2P) communication data is determined to be incorrect.
Supposed
Causes
Defective fan PCB (A2P)
Defective connection of capacity setting adaptor
Field setting error
Troubleshooting
NO
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Has the
indoor unit control PCB
(A1P) been replaced with a
spare PCB?
YES
YES
YES
NO
NO
Was
the correct
capacity setting
adaptor installed when
replacing it with a spare
PCB?
After establishing
transmission for indoor and
outdoor, diagnose the
operation again.
After establishing
transmission for indoor and
outdoor, diagnose the
operation again.
Replace it with the correct
fan PCB (A2P).
Install the correct capacity
setting adaptor.
Does the
fan PCB part No.
match that of the spare
parts list?