Troubleshooting by Error Code
SiME332106E
216
Part 6 Service Diagnosis
Note(s)
Reference
1. Error codes and thermistors
CHECK 11
Refer to page 281.
Error
Code
Applicable Thermistor
RXYMQ-A
Electric symbol
Connector
H9
Outdoor air thermistor
R1T
X18A
J3
Discharge pipe thermistor
R21T
X19A
J5
Suction pipe thermistor
R3T
X30A (Group
connector)
J6
Heat exchanger deicer thermistor
R7T
J7
Subcooling heat exchanger liquid pipe thermistor
R5T
J8
Heat exchanger liquid pipe thermistor
R4T
J9
Subcooling heat exchanger gas pipe thermistor
R6T