Troubleshooting by Error Code
SiME332106E
222
Part 6 Service Diagnosis
5.41 Inverter Radiation Fin Temperature Rise Abnormality
Applicable
Models
All outdoor unit models
Error Code
L4
Method of Error
Detection
Detect temperature of power module of the inverter circuit.
Error Decision
Conditions
Thermistor located inside the power module of the inverter circuit for compressor and fan motor.
Cooling tube plate poor heat-exchange.
Supposed
Causes
Radiation fin temperature rise of fan circuit
Cooling tube plate not fixed with screws
U0
error
Defective inverter circuit
High outdoor air temperature
Closed stop valve
Troubleshooting
Subcode L4-01
Defective radiation from the power
unit
• Blocked air suction port
• Stained radiation fin
• High outdoor air temperature
Connect the connector correctly.
Eliminate
P4
error.
Keep operating.
Replace the relevant PCB
(
1).
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Caution
YES
YES
YES
YES
NO
NO
NO
NO
Is the radiation fin
temperature greater than the
designed temperature?
Does the remote
controller display error
code
P4
?
Does the
connector X111A of fin
thermistor connect to the
outdoor unit main PCB
correctly?
When the unit starts
operating, is the error code
L4
displayed again?
Connect to the power and then press
the
INSPECTION/TEST
button on
remote controller.
NO
Open the stop valve.
YES
Is the stop valve open?