Refrigerant Circuit (Piping Diagrams)
SiME332106E
18
Part 2 Refrigerant Circuit
1.2
VRV
Indoor Unit
No. in piping
diagram
Name
Electric
symbol
Applicable model
Function
(1)
Electronic expansion valve
Y1E
All indoor units
Used for gas superheating degree
control while in cooling or subcooling
degree control while in heating.
(2)
Suction air thermistor
R1T
All indoor units
Used for thermostat control.
(3)
Indoor liquid pipe thermistor
R2T
All indoor units
Used for gas superheating degree
control while in cooling or subcooling
degree control while in heating.
(4)
Indoor gas pipe thermistor
R3T
All indoor units
Used for gas superheating degree
control while in cooling.
FXFSQ-AR
FXDQ-PD, FXDQ-ND
FXMQ-PB
FXMQ-AR
C: 4D121746
(1)
(3)
(4)
(2)
C: 4D115598B
(3)
(2)
(1)
(4)
(3)
(2)
(1)
(4)
C: 4D110285
C: 4D097585B
(2)
(1)
(3)
(4)