SiME332106E
Troubleshooting by Error Code
Part 6 Service Diagnosis
241
5.53 Refrigerant Shortage Warning (Heating)
Applicable
Models
RXYMQ4-6AYFK
Error Code
U0
Sub code: 06
Method of Error
Detection
Detects refrigerant shortage according to the difference between low pressure equivalent
saturation temperature and suction pipe temperature, opening degree of main electronic
expansion valve, or superheating operation.
Error Decision
Conditions
The following conditions are satisfied for 20 minutes or more.
Suction pipe temperature – Low pressure equivalent saturation temperature > 30°C
Opening degree of main electronic expansion valve (Y1E) > 480 pulses
Discharge pipe temperature > 125°C, or low pressure < 0.15 MPa and high pressure < 2.1
MPa simultaneously.
No abnormality is determined, and the operation continues.
Supposed
Causes
Refrigerant shortage and refrigerant clogging (wrong piping)
Defective thermistor
Defective low pressure sensor
Defective outdoor unit main PCB