Troubleshooting by Error Code
SiME332106E
242
Part 6 Service Diagnosis
Reference
Reference
Reference
Troubleshooting
CHECK 2
Refer to page 272.
CHECK 3
Refer to page 273.
CHECK 7
Refer to page 279.
Replace the thermistor
(R3T).
NO
Replace the outdoor unit
main PCB (A1P).
YES
YES
Are the
characteristics of the
suction pipe thermistor
normal?
NO
Are the
characteristics of the
low pressure sensor
normal?
Replace the low pressure
sensor (S1NPL).
Correct the abnormally low
pressure.
Correct the insufficient low
refrigerant condition.
Correct the superheat
operation.
NO
YES
Is refrigerant shortage detected
as a cause of abnormally
low pressure?
NO
YES
YES
YES
Is refrigerant
insufficient?
NO
NO
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
CHECK 2
Is another cause detected as a
cause of abnormally low
pressure?
CHECK 2
Is refrigerant shortage detected
as a cause of superheat
operation?
CHECK 3
CHECK 7
Is another cause detected
as a cause of superheat
operation?
CHECK 3