Troubleshooting by Error Code
SiME332106E
244
Part 6 Service Diagnosis
Note(s)
Reference
1. RXYMQ4AVMK: outdoor unit main PCB (A1P)
RXYMQ4-6AYFK: inverter PCB (A3P)
2. RXYMQ4AVMK: outdoor unit main PCB (A1P)
RXYMQ4-6AYFK: outdoor unit main PCB (A1P) and inverter PCB (A3P)
CHECK 2
Refer to page 272.
YES
Are the
characteristics of
the inverter fin temperature
thermistor normal?
(Refer to
L4
troubleshooting.)
Replace the relevant PCB
(
1).
NO
YES
Replace the low pressure
sensor (S1NPL).
NO
YES
Replace the high pressure
sensor (S1NPH).
NO
NO
Replace the relevant
PCB(s) (
2).
If the error recurs, replace
the electronic expansion
valve (refrigerant jacket)
(Y3E).
YES
Replace the electronic
expansion valve coil (Y3E).
Correct the abnormally low
pressure.
Correct the insufficient low
refrigerant condition.
Correct the superheating
operation.
NO
YES
Is refrigerant shortage detected
as a cause of abnormally
low pressure?
Are the characteristics and
insulation of the electronic expansion
valve (refrigerant jacket)
(Y3E) normal?
Are the characteristics
of the high pressure
sensor normal?
NO
YES
YES
YES
Is refrigerant
insufficient?
NO
NO
YES
NO
CHECK 2
Is another cause detected as a
cause of abnormally low
pressure?
CHECK 2
Is refrigerant shortage detected
as a cause of superheating
operation?
CHECK 3
CHECK 7
Is another cause detected
as a cause of superheating
operation?
CHECK 3
CHECK 18
CHECK 12
Are the characteristics
of the low pressure
sensor normal?
CHECK 12
A