SiME332106E
Troubleshooting by Error Code
Part 6 Service Diagnosis
257
NO
NO
YES
YES
NO
YES
YES
Connect the power supply cable
of the external control adaptor
for outdoor unit to the 16 VDC
power supply line.
Replace the outdoor unit main
PCB (A1P).
Replace the external control
adaptor PCB.
Replace the outdoor unit
main PCB (A1P).
NO
NO
YES
Modify the transmission wirings
to the external control adaptor for
outdoor unit.
Diagnosis Flowchart-1
Supply power to the outdoor
unit.
Is power supplied to
the outdoor unit?
Is the
microcomputer
normal monitor on the
outdoor unit main PCB
blinking?
Is the
microcomputer
normal monitor on the
external control adaptor
for outdoor unit
blinking?
(Transmission error when the
external control adaptor is mounted)
Is the
power supply
cable of the external
control adaptor for outdoor
unit connected to the
16 VDC power
supply line?
Is
there any
wiring
disconnection or wiring
error in the transmission
wirings to the external
control adaptor for
outdoor unit?
Error code
Sub code
U7-01