SiME332106E
Protection Control
Part 4 Functions and Control
63
Radiation fin temperature control
This control is performed for each compressor.
Cooling
Condition
All compressors
A
more than 91 °C
B
less than 89 °C
C
more than 110 °C
Heating
Condition
All compressors
A
more than 86.5 °C
B
less than 83.5 °C
C
more than 110 °C
Normal control
Fin temperature standby
Reduce compressor capacity
When occurring 4 times within 60
minutes, the error code
L4
is output.
A
B
C