7.2.2 Oil Return Control in Heating Operation
Part Name
Electric
Symbol
RXYMQ-A
Function
Compressor motor
M1C
RXYMQ4AVMK: 70 rps
RXYMQ4-6AYFK: 79 rps
Fan motor
M1F
With high pressure
OFF ←→ Step 4 ←→ Step 6
Electronic expansion valve
(Main)
Y1E
480 pulses
Electronic expansion valve
(Injection)
Y2E
0 pulse
Electronic expansion valve
(Refrigerant jacket)
Y3E
480 pulse
(0-480 pulse, when radiation fin temperature
increases)
Electronic expansion valve
(Refrigerant auto charge)
Y4E
480 pulse
Four way valve
Y1S
OFF
Ending conditions
• A lapse of 6 min.
• Ts–Te < 3°C
OR
Indoor unit actuator
Heating oil return control
Fan
Thermostat ON unit
OFF
Stopping unit
OFF
Thermostat OFF unit
OFF
Electronic expansion valve
Thermostat ON unit
Oil return EV opening degree
Stopping unit
Oil return EV opening degree
Thermostat OFF unit
Oil return EV opening degree