Outline of Control (Indoor Unit)
Part 4 Functions and Control
71
8.2.3 Thermostat Control with Operation Mode Set to "AUTO"
When the operation mode is set to "AUTO" on the remote controller, the system will conduct the
temperature control shown below.
Furthermore, setting changes of the differential value (
D
°C) can be made according to
information in the
Field Settings from Remote Controller
on page 84 and later.
: Factory setting
Mode
No.
First code
No.
Description
Second code No.
01
02
03
04
05
06
07
08
12
(22)
4
Automatic mode differential
0°C
1°C 2°C 3°C 4°C 5°C 6°C 7°C
2
D
Differential value: 0
°
C
27
°
C
25
°
C
30
°
C
Heating mode
Cooling mode
Control temp.
Differential value set to 1
°
C
26
°
C
24.5
°
C
29
°
C
Set heating temp.
27
°
C
Set cooling temp.
Heating mode
Cooling mode
Control temp.
Differential value set to 2
°
C
24
°
C
28
°
C
Heating mode
Cooling mode
Control temp.
Differential value set to 3
°
C
23.5
°
C
Heating mode
Cooling mode
Control temp.
25
°
C
Set heating temp.
27
°
C
Set cooling temp.
24
°
C
Set heating temp.
27
°
C
Set cooling temp.
Differential value set to 4
°
C
26
°
C
Heating mode
Cooling mode
Control temp.
Differential value set to 5
°
C
22
°
C
22.5
°
C 25
°
C
Set heating temp.
27
°
C
Set cooling temp.
Heating mode
Cooling mode
Control temp.
Differential value set to 6
°
C
22
°
C
24
°
C
Heating mode
Cooling mode
Control temp.
Differential value set to 7
°
C
21.5
°
C 23
°
C
Heating mode
Cooling mode
Control temp.
21
°
C
Set heating temp.
27
°
C
Set cooling temp.
20
°
C
Set heating temp.
27
°
C
Set cooling temp.
23
°
C
Set heating temp.
27
°
C
Set cooling temp.
(Ex.) When automatic cooling temperature is set to 27
°
C:
D
°
C
3
°
C
( + 2)
°
C
Set heating temperature
(A – D)
°
C
Set cooling temperature
A
°
C
Cooling thermostat ON
Cooling thermostat OFF
Display change
Heating
→
Cooling
Display change
Cooling
→
Heating
Heating thermostat OFF
Heating thermostat ON
Set cooling/
heating temp.