Outline of Control (Indoor Unit)
SiME332106E
72
Part 4 Functions and Control
8.3 Automatic Airflow Rate Control
The automatic airflow rate control (Five steps from H to L) is based on the difference between
control target temperature and set temperature.
1. LL airflow for FXFSQ-AR
Conditions
When airflow rate is set
Automatic airflow rate
Cooling
Thermostat ON
Set
The fan tap is determined
by the difference between control target
temperature and set temperature.
Thermostat OFF
Set (
1)
The fan keeps rotating at
the speed as just before
the thermostat off (
1)
Heating
Thermostat ON
Set
The fan tap is determined
by the difference between control target
temperature and set temperature.
Thermostat OFF
LL
LL
Program dry
Thermostat ON
L
L
Thermostat OFF
OFF
OFF
Fan
Set
M
Stop
OFF
OFF
H
HM
M
ML
L
Fan tap
Large
Difference between control target
Small
temperature and set temperature
<Change in airflow rate under
automatic airflow rate control>
Except for FXFSQ-AR,
HM and ML taps appear
only during the auto
airflow rate control
operation.
(For FXFSQ-AR,
HM and ML taps can be
manually set with remote
controller.)