Outline of Control (Indoor Unit)
SiME332106E
74
Part 4 Functions and Control
8.5 Auto Draft Reducing Control (FXFSQ-AR only)
In the case where both this control is activated and auto airflow direction control (eco full
automatic control) is set, when human presence is detected, the airflow direction is
automatically set to horizontal (P0) to reduce discomfort by direct airflow.
This control works for each airflow outlet individually.
Note: This function is inoperative for the airflow outlet where an individual airflow direction is set.
8.6 Eco Full Automatic Control (FXFSQ-AR only)
This is a generic term for the setting where both fan speed and airflow direction are set to
"Auto". For detailed control contents, refer to
Automatic Airflow Rate Control
and
Airflow
Direction Control
.
P0
P1
P2
P3
P4
Indoor
u
nit
AIR
Flap position
(Horizontal
v
ie
w
)
P0 (horizontal)
When presence is detected
Absence continues for 5 mins
Airflow direction by auto airflow direction
Cooling: P0 or P1
Heating: P3 or P4