SiME332106E
Outline of Control (Indoor Unit)
Part 4 Functions and Control
81
8.11.3 Operational Concept (Designer Panel)
8.12 Hot Start Control (In Heating Operation Only)
At startup with thermostat ON or after the completion of defrosting in heating operation, the
indoor fan is controlled to prevent cold air from blasting out and ensure startup capacity.
TH2 : Temperature detected with the gas thermistor
Tc : High pressure equivalent saturated temperature
Cooling
: Factory setting
Movement pattern
(a)
(b)
(c)
(d)
Appearance
Time
(seconds)
13 (23)-14
01: Pattern 1
120
600
120
600
02: Pattern 2
120
600
0
0
03: Pattern 3
0
0
120
600
04: Pattern 4
120
600
120
600
Heating
: Factory setting
Movement pattern
(a)
(b)
(c)
(d)
Appearance
Time
(seconds)
13 (23)-14
01: Pattern 1
120
120
120
120
02: Pattern 2
120
120
0
0
03: Pattern 3
0
0
120
120
04: Pattern 4
120
0
120
0
Indicates the horizontal flap is in the position of reducing airflow volume (the flap is inverted).
Indicates the horizontal flap is in the position of reducing airflow volume (the flap is inverted).
The fan is not OFF before initiating the hot start: LL
The fan is OFF before initiating the hot start: OFF
Hot start control
Hot start in progress
Normal control
Normal control
H/L remote
controller setting
LL
OFF
Remote controller
setting
P0 (Horizontal)
Fa
n
Louv
er
Ending condition
·
Lapse of 3 minutes
·
TH2 > 34˚C
·
Tc > 52˚C
OR
Starting condition
·
Defrost ending
·
Oil return ending
·
Thermostat ON
OR