Field Settings for Indoor Unit
Part 5 Field Settings and Test Operation
91
Note(s)
1. Settings are made simultaneously for the entire group, however, if you select the mode No. inside
parentheses, you can also set by each individual unit. Setting changes however cannot be checked except
in the individual mode for those in parentheses.
2. The mode numbers inside parentheses cannot be used by wireless remote controllers, so they cannot
be set individually. Setting changes also cannot be checked.
3. Do not make settings other than those described above. Nothing is displayed for functions the indoor unit
is not equipped with.
4.
88
or
Checking the connection. Please stand by.
may be displayed to indicate the remote controller is
resetting when returning to normal mode.
5. BRC1H81 series only
13 (23)
0
Ceiling height setting, Setting of
normal airflow
Refer to the page on the right for details.
1
Airflow direction setting
4-way airflow
3-way airflow
2-way airflow
—
2
Swing pattern settings
All direction
synchronized
swing
—
Facing
swing
—
3
(
5)
Airflow function setting
Equipped
Not equipped
—
—
—
4
Airflow direction adjustment
range
Refer to the page on the right for details.
5
Setting of static pressure
selection
Standard
High static
pressure
—
—
6
External static pressure
settings
Refer to the page on the right for details.
7
Setting of swing patterns when
cooling thermostat is OFF
Refer to the page on the right for details.
13
Setting of circulation airflow
Disabled
Enabled
—
—
14
Circulation airflow patterns
Pattern 1
Pattern 2
Pattern 3
Pattern 4
15
Switching panel type
Standard
panel
Designer panel
—
—
15 (25)
1
Humidification when heating
thermostat is OFF
Not equipped
Equipped
—
—
2
Direct duct connection
Not equipped
Equipped
—
—
3
Drain pump and humidifier
interlock selection
Not
interlocked
Interlocked
—
—
5
Individual ventilation setting
Normal
Individual
—
—
1b
4
Display of error codes on the
remote controller
—
Two-digit display
—
Four-digit
display
14
Setting restricted/permitted of
airflow block
Refer to the page on the right for details.
1c
0
Room temperature display
Not displayed
Displayed
—
—
01
(
5)
Thermostat sensor
Indoor unit
thermistor
Controller
thermistor
—
—
—
12
(
5)
Window contact B1
Do not use
Use
—
—
—
13
(
5)
Key card contact B2
Do not use
Use
—
—
—
1e
(
5)
02
Setback function
No Setback
Heating only
Cooling only
Heating and
Cooling
—
07
Rotation overlap time
30 minutes
15 minutes
10 minutes
5 minutes
—
1B
(
5)
08
Daylight saving time
Disable
Automatic
changeover
Manual
changeover
Centralized
control
—
Mode
No.
(
2)
First
Code
No.
Description
Second Code No.
Reference
Page
01
02
03
04