Field Settings for Indoor Unit
Part 5 Field Settings and Test Operation
103
1.4.27 External Static Pressure Settings
Make external static pressure setting automatically using automatic airflow adjustment
(11 (21)-7), or manually using external static pressure settings (13 (23)-6).
FXMQ-PB
: Factory setting
1 FXMQ40PB cannot be set to 180 or 200 Pa.
2 FXMQ50-125PB cannot be set to 30 Pa.
3 FXMQ140PB cannot be set to 30 Pa and 150-200 Pa.
1.4.28 Setting of Swing Patterns when Cooling Thermostat is OFF
In cooling operation, when the airflow direction is set to swing, flaps swing even when the
thermostat is OFF. This setting allows to change the airflow direction when the thermostat is
OFF.
: Factory setting
1.4.29 Setting of Circulation Airflow
This is to set whether the circulation airflow function is enabled or disabled.
: Factory setting
Mode No.
First Code No.
Second Code No.
Contents
13 (23)
6
01
30 Pa (
2) (
3)
02
50 Pa
03
60 Pa
04
70 Pa
05
80 Pa
06
90 Pa
07
100 Pa
08
110 Pa
09
120 Pa
10
130 Pa
11
140 Pa
12
150 Pa (
3)
13
160 Pa (
3)
14
180 Pa (
1) (
3)
15
200 Pa (
1) (
3)
Mode
No.
First
Code No.
Second
Code No.
Fixed
Swing
13 (23)
7
01
Set Position
Swing
02
Set Position
P0
03
P0
P0
04
Set Position
Swing
05
Set Position
P2
06
P2
P2
07
Set Position
Swing
Mode
No.
First
Code No.
Second
Code No.
Contents
13 (23)
13
01
Disabled
02
Enabled