Field Settings for Indoor Unit
SiME332106E
104
Part 5 Field Settings and Test Operation
1.4.30 Circulation Airflow Patterns
This setting is to change the appearance pattern of the circulation airflow direction depending
on the installation environment of the indoor unit.
1.4.31 Switching Panel Type
Change this setting depending on the type of the panel connected.
: Factory setting
1.4.32 Humidification when Heating Thermostat is OFF
Setting to
Equipped
turns ON the humidifier if suction air temperature is 20ºC or more and turns
OFF the humidifier if suction air temperature is 18ºC or below when the heating thermostat is
OFF.
: Factory setting
Cooling
: Factory setting
Movement pattern
(a)
(b)
(c)
(d)
Appearance
Time (sec.)
13 (23)-14
01: Pattern 1
120
600
120
600
02: Pattern 2
120
600
0
0
03: Pattern 3
0
0
120
600
04: Pattern 4
120
600
120
600
Indicates the horizontal flap is in the position of reducing airflow volume (where the flap is
reversed).
Heating
: Factory setting
Movement pattern
(a)
(b)
(c)
(d)
Appearance
Time (sec.)
13 (23)-14
01: Pattern 1
120
120
120
120
02: Pattern 2
120
120
0
0
03: Pattern 3
0
0
120
120
04: Pattern 4
120
0
120
0
Indicates the horizontal flap is in the position of reducing airflow volume (where the flap is
reversed).
Mode
No.
First
Code No.
Second
Code No.
Contents
13 (23)
15
01
Standard panel
02
Designer panel
Mode
No.
First Code
No.
Second Code
No.
Contents
15 (25)
1
01
Not equipped
02
Equipped