Troubleshooting by Error Code
SiME332106E
230
Part 6 Service Diagnosis
Note(s)
5.45 Transmission Error between Microcomputers on
Outdoor Unit Main PCB
Applicable
Models
RXYMQ4AVMK
Error Code
LC
Method of Error
Detection
Check for the transmission conditions between microcomputers on the outdoor unit main PCB
using a microcomputer.
Error Decision
Conditions
Normal transmission is disabled for a given period of time or more.
Supposed
Causes
Connection error between microcomputers on the outdoor unit main PCB
Defective outdoor unit main PCB (transmission block)
Defective noise filter
External factors (e.g. noise)
Defective compressor
Defective fan motor
Troubleshooting
Properly connect the harness.
NO
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Is the harness
between terminal block
and outdoor unit main PCB
securely connected?
(
1)
Replace the outdoor unit main PCB
(A1P).
NO
YES
The
microcomputer normal
monitor (green) on the outdoor
unit main PCB (A1P) is
blinking.
NO
Replace the outdoor unit main PCB
(A1P).
YES
Continue operation.
The error could have resulted from
causes such as instantaneous
power failure.
The
LC
error recurs.
Replace the fan motor.
YES
NO
The insulation
resistance of the
compressor is less than
100 k
.
The insulation
resistance of the fan motor
is less than
1 M
Replace the compressor.
YES
NO
1. Connect and disconnect the connector once to ensure that it is securely connected.