Field Settings for Indoor Unit
SiME332106E
90
Part 5 Field Settings and Test Operation
1.2 List of Field Settings for Indoor Unit
: Factory setting
Mode
No.
(
2)
First
Code
No.
Description
Second Code No.
Reference
Page
01
02
03
04
10 (20)
0
Filter
cleaning
sign interval
Ultra long life
filter
Light
Approx.
10,000
hrs.
Heavy
Approx.
5,000
hrs.
—
—
Long life filter
Approx.
2,500
hrs.
Approx.
1,250
hrs.
Standard filter
Approx.
200
hrs.
Approx.
100 hrs.
1
Filter type
Long life filter
Ultra long life
filter
—
—
2
Remote controller thermistor
Remote
controller
ther
Suction air
thermistor
Only suction air
thermistor
Only remote
controller
thermistor
—
3
Filter cleaning sign
Displayed
Not displayed
—
—
5
Information for intelligent Touch
Manager / intelligent Touch
Controller
Refer to the page on the right for details.
6
Remote controller thermistor
control during group control
Not permitted
Permitted
—
—
7
Time for absence area
detection
30 minutes
60 minutes
—
—
10
Dry operation time during
VRTsmart control
30 minutes
60 minutes
90 minutes
Continuous
(not returning
to cooling)
11
Low airflow setting when
thermostat OFF during
VRTsmart control
Disabled
Enabled
—
—
11 (21)
2
Indoor fan settings during
cooling/heating thermostat OFF
Normal
Fan OFF
—
—
3
Setting of airflow rate when
heating
Standard
Slightly
increased
Increased
—
6
Setting the rate of human
detection
High sensitivity
Low sensitivity
Standard
sensitivity
Infrared
presence
sensor
disabled
7
Automatic airflow adjustment
OFF
Completion of
airflow
adjustment
Start of
airflow
adjustment
—
8
Compensating the temperature
around people
Suction air
temperature only
Priority given on
the suction air
temperature
Standard
Priority given
on the floor
temperature
9
Compensating the floor
temperature when heating
–4°C
–2°C
0°C
2°C
12 (22)
0
Optional accessories output
selection
Indoor unit
turned ON by
thermostat
—
Operation
output
Error output
1
External ON/OFF input
Forced OFF
ON/OFF control
External
protection
device input
—
2
Thermostat differential
changeover
1°C
0.5°C
—
—
3
Airflow setting when heating
thermostat is OFF
LL tap
Set fan speed
—
—
4
Automatic mode differential
Refer to the page on the right for details.
5
Auto restart after power failure
OFF
ON
—
—
6
Airflow setting when cooling
thermostat is OFF
LL tap
Set fan speed
—
—
11
Compensating the floor
temperature when cooling
4°C
2°C
0°C
–2°C