• VRV
®
Systems • Outdoor Units
9
• Outdoor Units • VRV
®
Heat Pump • RXYQ5-54P7W1B(A)
1
Specifications
3
Piping
connections
Liquid (OD)
Type
Braze connection
Diameter (OD)
mm
19.1
19.1
19.1
19.1
Gas
Type
Braze connection
Diameter (OD)
mm
41.3
41.3
41.3
41.3
Heat Insulation
Both liquid and gas pipes
Max total length
m
1000
1000
1000
1000
Defrost Method
Reversed cycle
Defrost Control
Sensor for outdoor heat exchanger temperature
Capacity Control Method
Inverter controlled
Capacity Control
~ 100
Safety devices
HPS
Fan motor driver overload protector
Over current relay
Inverter overload protector
PC board fuse
Standard
Accessories
Standard Accessories
Installation and operation manual
Quantity
1
1
1
1
Standard Accessories
Connection pipes
Quantity
4
4
4
4
Notes
Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature :
35°CDB, equivalent refrigerant piping : 7.5m, level difference : 0m.
Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB,
equivalent refrigerant piping : 7.5m, level difference : 0m
Sound level of a multi system is determined by the individual outdoor unit and installation condition
The refrigerant charge of the system must be less than 100 kg. This means that in case the calculated refrigerant
charge is equal to or more than 95 kg, you must divide your multiple outdoor system into smaller independent
systems, each containing less than 95 kg refrigerant charge. For factory charge, refer to the namplate of the unit.
1-2 TECHNICAL SPECIFICATIONS
RXYQ48P7W1BA
RXYQ50P7W1BA
RXYQ52P7W1BA
RXYQ54P7W1BA