• Outdoor Units • VRV
®
Heat Pump • RXYQ5-54P7W1B(A)
• VRV
®
Systems • Outdoor Units
10
1
Specifications
3
1-3 ELECTRICAL SPECIFICATIONS
RXYQ5P7W1B
RXYQ8P7W1B
RXYQ10P7W1B
RXYQ12P7W1B
RXYQ14P7W1BA RXYQ16P7W1BA RXYQ18P7W1BA
Power Supply
Name
W1
Phase
3N~
Frequency
Hz
50
50
5
50
50
50
50
Voltage
V
400
400
400
400
400
400
400
Current
Nominal
running current
(RLA)
Cooling
A
5.1
7.5
11.3
14.0
18.4
21.3
24.2
Heating
A
5.8
8.2
11.1
13.8
16.8
19.4
23.0
Starting current (MSC)
A
74
75
84
85
85
Minimum Ssc value
kVa
1,218
928
944
1,114
1,114
1,171
Minimum circuit amps (MCA)
A
11.9
18.5
21.6
22.7
31.5
31.5
32.5
Maximum fuse amps (MFA)
A
16
25
25
25
40
40
40
Total overcurrent amps (TOCA)
A
15.6
16.5
31.5
31.5
46.4
46.4
48.3
Full load amps (FLA)
A
0.4
0.7
0.9
0.9
1.2
1.2
1.4
Voltage range
Minimum
V
360
360
360
360
360
360
360
Maximum
V
440
440
440
440
440
440
440
Wiring
connections
For Power
Supply
Quantity
5
5
5
5
5
5
5
Remark
Earth wire included
For connection
with indoor
Quantity
2
2
2
2
2
2
2
Remark
F1 - F2
Power Supply Intake
Both indoor and outdoor unit
Notes
MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker)
MSC means the maximum current during start up of the compressor
Maximum allowable voltage range variation between phases is 2%
RLA is based on following conditions : indoor temperature : 27°CDB/19°CWB , outdoor temperature : 35°CDB
Select wire size based on the value of MCA or TOCA
TOCA means the total value of each OC set
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminal is not below
or above listed range limits
1-3 ELECTRICAL SPECIFICATIONS
RXYQ20P7W1B
RXYQ22P7W1B
RXYQ24P7W1B
RXYQ26P7W1BA
RXYQ28P7W1BA
RXYQ30P7W1BA
RXYQ32P7W1BA
Power Supply
Name
W1
Phase
3N~
Frequency
Hz
50
50
50
50
50
50
50
Voltage
V
400
400
400
400
400
400
400
Current
Nominal running
current (RLA)
Cooling
A
21.4
25.3
28.0
31.7
35.6
38.2
42.7
Heating
A
22.0
24.8
27.5
31.2
34.1
36.8
39.8
Starting current (MSC)
A
79
88
88
89
98
98
108
Minimum circuit amps (MCA)
A
41.2
44.3
45.4
51.0
54.1
55.2
64.0
Maximum fuse amps (MFA)
A
50
50
50
63
63
63
80
Total overcurrent amps (TOCA)
A
48.0
63.0
63.0
64.8
79.8
79.8
94.7
Full load amps (FLA)
A
1.6
1.8
1.8
2.1
2.3
2.3
2.6
Voltage range
Minimum
V
360
360
360
360
360
360
360
Maximum
V
440
440
440
440
440
440
440
Wiring
connections
For Power
Supply
Quantity
5
5
5
5
5
5
5
Remark
Earth wire included
For connection
with indoor
Quantity
2
2
2
2
2
2
2
Remark
F1 - F2
Power Supply Intake
Both indoor and outdoor unit
Notes
MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker)
MSC means the maximum current during start up of the compressor
Maximum allowable voltage range variation between phases is 2%
RLA is based on following conditions : indoor temperature : 27°CDB/19°CWB , outdoor temperature : 35°CDB
Select wire size based on the value of MCA or TOCA
TOCA means the total value of each OC set
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminal is not below
or above listed range limits