• VRV
®
Systems • Outdoor Units
11
• Outdoor Units • VRV
®
Heat Pump • RXYQ5-54P7W1B(A)
1
Specifications
3
1-3 ELECTRICAL SPECIFICATIONS
RXYQ34P7W1BA
RXYQ36P7W1BA
RXYQ38P7W1BA
RXYQ40P7W1BA
RXYQ42P7W1BA
RXYQ44P7W1BA
RXYQ46P7W1BA
Power Supply
Name
W1
Phase
3N~
Frequency
Hz
50
50
50
50
50
50
50
Voltage
V
400
400
400
400
400
400
400
Current
Nominal running
current (RLA)
Cooling
A
45.5
48.5
45.7
49.5
52.2
55.9
59.8
Heating
A
42.4
46.0
45.0
47.8
50.5
54.2
57.1
Starting current (MSC)
A
109
109
102
111
111
113
122
Minimum circuit amps (MCA)
A
64.0
65.0
73.7
76.8
77.9
83.5
86.6
Maximum fuse amps (MFA)
A
80
80
100
100
100
100
100
Total overcurrent amps (TOCA)
A
94.7
96.6
96.3
111.3
111.3
113.1
128.1
Full load amps (FLA)
A
2.6
2.8
3.0
3.2
3.2
3.5
3.7
Voltage range
Minimum
V
360
360
360
360
360
360
360
Maximum
V
440
440
440
440
440
440
440
Wiring
connections
For Power
Supply
Quantity
5
5
5
5
5
5
5
Remark
Earth wire included
For connection
with indoor
Quantity
2
2
2
2
2
2
2
Remark
F1 - F2
Power Supply Intake
Both indoor and outdoor unit
Notes
MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker)
MSC means the maximum current during start up of the compressor
Maximum allowable voltage range variation between phases is 2%
RLA is based on following conditions : indoor temperature : 27°CDB/19°CWB , outdoor temperature : 35°CDB
Select wire size based on the value of MCA or TOCA
TOCA means the total value of each OC set
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminal is not below
or above listed range limits
1-3 ELECTRICAL SPECIFICATIONS
RXYQ48P7W1BA
RXYQ50P7W1BA
RXYQ52P7W1BA
RXYQ54P7W1BA
Power Supply
Name
W1
Phase
3N~
Frequency
Hz
50
50
50
50
Voltage
V
400
400
400
400
Current
Nominal
running current
(RLA)
Cooling
A
62.5
66.9
69.8
72.7
Heating
A
59.8
62.8
65.4
69.0
Starting current (MSC)
A
122
132
134
134
Minimum circuit amps (MCA)
A
87.7
96.5
96.5
97.5
Maximum fuse amps (MFA)
A
100
125
125
125
Total overcurrent amps (TOCA)
A
128.1
143.0
143.0
144.9
Full load amps (FLA)
A
3.7
3.6
3.6
4.2
Voltage range
Minimum
V
360
360
360
360
Maximum
V
440
440
440
440
Wiring
connections
For Power
Supply
Quantity
5
5
5
5
Remark
Earth wire included
For connection
with indoor
Quantity
2
2
2
2
Remark
F1 - F2
Power Supply Intake
Both indoor and outdoor unit
Notes
MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker)
MSC means the maximum current during start up of the compressor
Maximum allowable voltage range variation between phases is 2%
RLA is based on following conditions : indoor temperature : 27°CDB/19°CWB , outdoor temperature : 35°CDB
Select wire size based on the value of MCA or TOCA
TOCA means the total value of each OC set
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminal is not below
or above listed range limits