English 14
Setting the Cool / Heat Changeover Master
Setting Changes
See page 14 for an explanation of the cool/heat changeover master indoor unit.
1
Cool
Return
Setting
Set to
Cool
74
F
Cool
Return
Setting
Set to
Cool
74
F
MASTER
CONTROLLED
●
Press the Operation Mode Selector button on the remote controller of the
changeover master indoor unit for at least four seconds while the backlight is
illuminated.
●
The “
MASTER
CONTROLLED
” icon on each remote controller for the indoor units connected to the same
outside unit or Branch Selector unit will start flashing.
* Vent mode setting changes are possible regardless of the cool/heat changeover master indoor unit.
*
If cool/heat mode is configured for control from the outside unit, all remote controllers serving the
associated indoor units will display its “
MASTER
CONTROLLED
” icon.
●
Set the cool/heat changeover master indoor unit as outlined below.
The icon “ ” will flash on all remote controllers when the power is turned ON for the first time.
Selection Settings
MASTER
CONTROLLED
2
Cool
Return
Setting
Set to
Cool
74
F
MASTER
CONTROLLED
Cool
Return
Setting
Set to
Cool
74
F
●
Press the Mode Selector button on the remote controller of the indoor unit
which is to serve as the cool/heat changeover master.
The remote controller for the changeover master indoor unit is established
and the
MASTER
CONTROLLED
icon is no longer displayed.
Other remote controllers in the system (indoor units served by the same
outside unit or indoor units served by the same Branch Selector unit) will
now display the
MASTER
CONTROLLED
icon.
3
Cool
Return
Setting
Set to
Cool
74
F
●
Press the Mode button on the remote controller of the indoor unit
designated as the cool/heat changeover master (the remote controller not
displaying the
MASTER
CONTROLLED
icon) repeatedly until the desired mode is selected.
The display will change to “Fan”, “Dry”, “Auto”, “Cool”, “Heat” each time
the button is pressed.
●
Simultaneously, the other indoor units on the system will follow suit and
change modes to reflect the new mode selected at the changeover master
remote controller.
Cool / Heat Mode Selection Availability
●
“Cool”, “Heat” and “Auto” are all only available for selection on the cool/heat changeover master indoor unit. The following
table indicates the available operating modes of the other indoor units on the system based upon the selected mode of the
master indoor unit.